Cookie policy: This site uses cookies (small files stored on your computer) to simplify and improve your experience of this website. Cookies are small text files stored on the device you are using to access this website. For more information on how we use and manage cookies please take a look at our privacy and cookie policies. Some parts of the site may not work properly if you choose not to accept cookies.


Data center cooling has evolved, so should design

  • Print
  • Share
  • Comment
  • Save

Driven by rising power densities and heat levels, data center cooling strategies have changed dramatically in recent years. Until relatively recently, most data center cooling schemes relied on so-called “chaos” air distribution methodologies, in which perimeter CRAC units pumped out massive volumes of chilled air that both cooled IT equipment and helped push hot server exhaust air towards the facility’s return air ducts. However, chaos air distribution commonly results in a wide range of significant inefficiencies, including:

Re-circulation: Typically caused by poor rack hygiene and insufficient cool air available at the face of the rack, hot exhaust air can find its way back into server air intakes, heating IT equipment to potentially dangerous temperatures.

Air stratification: In an attempt to provide cooler air at the top of the face of the rack, the natural tendency of air to mass in different temperature-based layers can force set points on precision cooling equipment to be lower than recommended. Often, in attempts to remediate air stratification, technicians increase the fan speed of CRAC units to deliver more cool air to the room, which can result in bypass air.

Bypass air: The velocity of the cool air stream exceeds the ability of the server fans to draw in the cool air; as a result the cool air shoots beyond the face of the IT rack.  Cool supply air can join the return air stream before passing through servers, weakening cooling efficiency.

Eager to combat the inefficiencies above and keep pace with steadily climbing data center temperatures, businesses often adopt hot aisle/cold aisle rack orientation arrangements, in which only hot air exhausts and cool air intakes face each other in a given row of server racks.

Such configurations generate convection currents that produce improved airflow. Although superior to chaos air distribution, hot aisle/cold aisle strategies have proven only marginally more capable of cooling today’s increasingly dense data centers, largely because both approaches ultimately share a common, fatal flaw: They allow air to move freely throughout the data center.

This flaw eventually led to the introduction of containment cooling strategies. Designed to organize and control air streams, containment solutions enclose server racks in sealed structures that capture hot exhaust air, vent it to the CRAC units and then deliver chilled air directly to the server equipment’s air intakes. The end result is a series of important benefits:

Improved cooling efficiency: By preventing the supply and return air streams from intermingling, well-designed containment solutions eliminate wasteful re-circulation, air stratification and bypass airflow.

Increased reliability: Eliminating re-circulation spares servers from exposure to potentially dangerous warm air that can result in thermal stress which decreases life of IT equipment

Lower energy spending: To counteract the effects of re-circulated exhaust air, legacy cooling schemes typically chill return air to 55ºF/12.78ºC. Containment-based cooling systems completely isolate return air, however, so they can safely deliver supply air at 65ºF/18.34ºC or higher. As a result, containment cooling strategies typically reduce CRAC unit power consumption by an average of 16 percent.

Greater floor plan flexibility: To generate the cooling convection currents that make hot aisle/cold aisle strategies work, companies must place their server racks in rigidly aligned, uniformly arranged rows. Containment strategies don’t rely on convection, however, so they empower data center designers to position enclosures in any configuration that best fits their needs.

Impact on design

Despite the revolutionary impact of containment strategies on data center cooling, most organizations continue to plan new computing facilities the same way they always have. First they design a building and devote some of it to the data hall, or white space. Then they fill the white space with as many server racks as it will hold.

Designing data centers in that traditional manner can create a wide range of problems. For example, an undersized or oversized power and cooling infrastructure can limit operating capacity or increase capital expenses. Inconveniently located structural elements can force containment ducts to bend and detour in ways that reduce their efficiency, and inadequate room dimensions can complicate server rack placement and produce wasted floor space.

As a result, companies are increasingly recognizing the wisdom of designing data centers not from the walls in but from the server rack out. Instead of building a room and then filling it with racks, they’re selecting the ideal racks for their needs and designing the room around them. Instead of under- or overprovisioning their new facility’s power and cooling resources, they’re installing the optimal infrastructure for the precise array of hardware and enclosures that they’ll be using. Instead of improvising solutions to efficiency-sapping structural defects, they’re preventing those defects from occurring in the first place. The end result is a data center that’s not only less costly to cool and maintain, but more reliable and better suited to business requirements.



Related images

  • A CFD design of a data center. Image supplied by Sudlows

Have your say

Please view our terms and conditions before submitting your comment.

  • Print
  • Share
  • Comment
  • Save


  • Overhead Power Distribution – Best Practice in Modular Design

    Tue, 10 Nov 2015 16:00:00

    Overhead power distribution in your data center offers many attractive possibilities but is not without its challenges. Join UE Corp’s Director of Marketing, Mark Swift, and CPI’s Senior Data Center Consultant, Steve Bornfield, for an exploration of the options and some of the pitfalls, supported by real-life examples from the field.

  • Overcoming the Challenges of High Power Density Deployments

    Wed, 4 Nov 2015 19:00:00

    Increasing rack power densities saves space and energy, and improves both OPEX and CAPEX. But it can also create unintended problems that could bring your data center to a screeching halt. Join Raritan’s VP of Products & Marketing, Henry Hsu, and DCD’s CTO Stephen Worn, as they reveal the three key challenges in deploying a high density cabinet, and explain how to: Reduce operating costs, Increase up-time , Improve mean time to repair, become more energy-efficient manage existing capacity and plan for growth.

  • Squeezing the Lemon - The Power to do More with Less

    Tue, 20 Oct 2015 08:00:00

    Energy costs rising, manpower resources falling – managing a data center is getting more stressful by the day. One cold night could be all it takes to tip your power supply over the edge. And let's not forget the never-ending demands from IT for additional space. More information on its own is not the answer. Join Rittal's webinar to understand how to: • Lower your power consumption and OPEX charges, with 'smart' power distribution • Identify issues before they become problems, with intelligent PDUs' monitoring capabilities • Expand your DC as your business grows, with modular PDUs • Profile your power requirements to help you plan and make better-informed decisions REGISTER NOW Note: All attendees will receive a free copy of the latest White Paper from Rittal.

  • Live Customer Roundtable: Optimizing Capacity (12:00 EST)

    Tue, 8 Sep 2015 16:00:00

    The biggest challenge facing many data centers today? Capacity. How to optimize what you have today. And when you need to expand, how to expand your capacity smarter. Learn from the experts about how Data Center Infrastructure Management (DCIM) and Prefabricated Modular Data Centers are driving best practices in how capacity is managed and optimized: - lower costs - improved efficiencies and performance - better IT services delivered to the business - accurate long-range planning Don;t miss out on our LIVE customer roundtable and your chance to pose questions to expert speakers from Commscope, VIRTUS and University of Montana. These enterprises are putting best practices to work today in the only place that counts – the real world.

  • Power Optimization – Can Your Business Survive an Unplanned Outage? (APAC)

    Wed, 26 Aug 2015 05:00:00

    Most outages are accidental; by adopting an intelligent power chain, you can help mitigate them and reduce your mean-time to repair. Join Anixter and DatacenterDynamics for a webinar on the five best practices and measurement techniques to help you obtain the performance data you need to optimize your power chain. Register today!

More link